LF-AM2/4 LON sensor/actuator module with 2 voltage inputs for active 0-10V sensors (temperature, electrical vent, valve positions, window monitoring, dewpoint monitoring), 2 voltage outputs 0-10V (controlling of motorized vent valves, electronic ballasts) and 2 digital outputs (2 SPST-NO, photoMOS relay).
TP/FT-10 free topology twisted pair (ISO/IEC 14908-2),
Supply voltage 20 V to 28 V AC/DC
| Category | I/O components, Mixed |
| Manufacturer | METZ Connect |
| Bus | LON-TP/FT-10 |
| Input/Output | 2x analog voltage in, 2x analog voltage out, 2x digital out |
| Measurement range (voltage) | 0 to 10 V DC |
| Resolution Input (voltage) | 10 mV (0 to 100 %) |
| Output voltage | 0 to 10 V DC |
| Resolution Output (voltage) | 10 mV (0 to 100 %) |
| Digital output | 2 SPST-NO, photoMOS relay |
| Switching voltage | max.40 V AC/DC |
| Continuous current | max. 100 mA |
| Mounting | Snap mounting on DIN rail according to DIN EN 50022 |
| EAN-No | 4250184135791 |