LON-Mixed (In/out voltage, digital out 100 mA)

LF-AM2/4 LON sensor/actuator module with 2 voltage inputs for active 0-10V sensors (temperature, electrical vent, valve positions, window monitoring, dewpoint monitoring), 2 voltage outputs 0-10V (controlling of motorized vent valves, electronic ballasts) and 2 digital outputs (2 SPST-NO, photoMOS relay).
TP/FT-10 free topology twisted pair (ISO/IEC 14908-2),
Supply voltage 20 V to 28 V AC/DC

LF-AM2/4

Specification

Category I/O components, Mixed
Manufacturer METZ Connect
Bus LON-TP/FT-10
Input/Output 2x analog voltage in, 2x analog voltage out, 2x digital out
Measurement range (voltage) 0 to 10 V DC
Resolution Input (voltage) 10 mV (0 to 100 %)
Output voltage 0 to 10 V DC
Resolution Output (voltage) 10 mV (0 to 100 %)
Digital output 2 SPST-NO, photoMOS relay
Switching voltage max.40 V AC/DC
Continuous current max. 100 mA
Mounting Snap mounting on DIN rail according to DIN EN 50022
EAN-No 4250184135791