SAM2 LON sensor/actuator module with 2 digital inputs for a blind-control switch and 2 interlocked outputs for motors with current ratings up to 3A. Intented for installation in a recessed socket.
LON Powerline C-Band interface as per DIN EN 14908-3 or ISO/IEC 14908-3.
Supply voltage 230V~/50Hz
Category | I/O components, Mixed |
Manufacturer | Secyourit |
Bus | LON-Powerline |
Input/Output | 2x digital input, 2x digital out (3A) |
Input voltage | 230V~/50Hz, power consumption 0.5W..1.5W via the L, N connector |
Input high signal | internally provided 15V input potential vs. N. |
Digital output | 2 x relay contacts to the electrical motor |
Switching voltage | 250 V AC |
Continuous current | 3 A / output |
EAN-No | 4260194734020 |