QuickServer M-Bus to BACnet/IP-MS/TP and Modbus RTU/TCP Gateway (64)

FieldServer QuickServer M-Bus to BACnet/IP-MS/TP and Modbus RTU/TCP Gateway (max. 64 M-Bus Slaves)

QuickServer M-Bus to BACnet IP

Description ↑ 

The QuickServer M-Bus Gateway is configurable to act as both a Master and a Slave M-Bus device. As M-Bus Master it polls data from the M-Bus network and publishes it to the BACnet or Modbus network. In slave mode it allows to exchange data from BACnet or ModBus into M-Bus network. In slave mode baud rate gets automatically adapted to the baud rate required by the master speed (auto-baud).

QuickServer Key Features:

  • Integrated M-Bus Level Converter for up to 64 M-Bus devices
  • M-Bus Baud Rate: 300-38400 baud (Auto-band Discovery)
  • BTL certification, Rev. 12
  • BACnet COV support for fast data communication while reducing traffic over a BACnet network
  • Multi-configuration capability; specific configurations selectable via DIP switches or software
  • DIP switches to select baud rate or node ID on the fly
  • Embedded diagnostics for data monitoring and control
  • Web Based GUI configuration
  • Flat panel mount standard, DIN rail mount option
  • Specification ↑ 

    Configuration M-Bus TO BACnet-IP
    Category Protocol Converter; Gateway
    Manufacturer Sierra Monitor
    Bus M-Bus; BACnet-IP
    Bus 1 M-Bus
    Bus 2 BACnet-IP
    Data Points 5000
    M-Bus Slaves 64
    Hardware FS-QS-1x50
    Characteristics BTL Mark (Version 1 Revision 12); Suppots Who-Is and I-Am Services, Who-Has and I-Have SErvices.
    BACnet Standardized Profile BACnet Application Specific Controller (B-ASC)
    BACnet Smart Sensor (B-SS)
    BACnet Smart Actuator (B-SA)
    Networking Options Annex H.2, Multiple “Virtual” BACnet Devices in a Single Physical Device
    BACnet/IP Broadcast Management Device - (BBMD)
    Registrations by Foreign Devices
    BACnet Services Read Property Service (DS-RP-A, DS-RP-B)
    Read Property Multiple Service (DS-RPM-A, DS-RPM-B)
    Alarm and Event-Notification Internal-B (AE-N-I-B)
    Alarm and Event-ACK-B (AE-ACK-B)
    Alarm and Event-Information-B (AE-INFO-B)
    Trending - Viewing and Modifying Trends Internal-B (T-VMT-I-B)
    Trending -Automated Trend Retrieval-B (T-ATR-B)
    Device Management - Dynamic Device Binding (DM-DDB-A, DM-DDB-B)
    Device Management - Dynamic Object Bindging (DM-DOB-A, DM-DOB-B)
    Device Management- Device Communication Control-B (DM-DDC-B)
    TimeSyncoronization-B (DM-TS-B)
    Device Management- Reinitialize Device B (DM-RD-B)
    Device Management- Restart-B (DM-R-B)
    Device Management - List Manipulation-B (DM-LM-B)
    M-Bus Baudrate 300,600,1200,2400,4800,9600,19200,38400
    Serial Port RS-485
    Power Requirements 9-30 VDC or 12-24 VAC
    Temperature -40 ... +75°C